Cable cross-section0.75 ... 10 mm²Cable entry positionUp/DownCable outlets per side2xM20 / 2xM20Connecting capacity main circuitScrew Clamp 0.75 ... 10 mm²Screw Clamp / PE Terminal 2pc,0.75 ... 2.5 mm²Conventional thermal currentFully Enclosed 25 ADegree of protectionacc. to IEC 60529 IP65Enclosure materialPlasticHandle colorBlackHandle TypeSelector handleImpact resistance ratingHousing IK08Maximum mounted auxiliary contacts1 NO, 1 NCMounted auxiliary contacts0 NO, 0 NCNeutral typeFixed neutralNumber of auxiliary contacts NC0Number of auxiliary contacts NO0Pollution degree3Position of line terminalsTop In - Bottom OutPosition of neutral terminalsTop In - Bottom OutPosition of PE terminalsTop In - Bottom OutRated impulse withstand voltage0.5 kVRated insulation voltageacc. to IEC/EN 60664-1 750 VRated operational current AC-21A(500 V) 16 A(380 ... 415 V) 16 A(690 V) 16 ARated operational current AC-22A(380 ... 415 V) 16 A(690 V) 16 ARated operational current AC-23A(380 ... 415 V) 16 A(500 V) 16 A(690 V) 10 ARated operational power AC-23A(380 ... 415 V) 7.5 kW(500 V) 7.5 kW(690 V) 7.5 kWRated operational voltageMain Circuit 750 VRated short-circuit making capacity(690 V AC) 0.705 kARated short-time withstand current low voltagefor 1 s 0.5 kATightening torqueMain Circuit 0.8 N·m
| Cable cross-section | 0.75 ... 10 mm² |
| Cable entry position | Up/Down |
| Cable outlets per side | 2xM20 / 2xM20 |
| Connecting capacity main circuit | Screw Clamp 0.75 ... 10 mm²Screw Clamp / PE Terminal 2pc,0.75 ... 2.5 mm² |
| Conventional thermal current | Fully Enclosed 25 A |
| Degree of protection | acc. to IEC 60529 IP65 |
| Enclosure material | Plastic |
| Handle color | Black |
| Handle Type | Selector handle |
| Impact resistance rating | Housing IK08 |
| Maximum mounted auxiliary contacts | 1 NO, 1 NC |
| Mounted auxiliary contacts | 0 NO, 0 NC |
| Neutral type | Fixed neutral |
| Number of auxiliary contacts NC | 0 |
| Number of auxiliary contacts NO | 0 |
| Pollution degree | 3 |
| Position of line terminals | Top In - Bottom Out |
| Position of neutral terminals | Top In - Bottom Out |
| Position of PE terminals | Top In - Bottom Out |
| Rated impulse withstand voltage | 0.5 kV |
| Rated insulation voltage | acc. to IEC/EN 60664-1 750 V |
| Rated operational current AC-21A | (500 V) 16 A(380 ... 415 V) 16 A(690 V) 16 A |
| Rated operational current AC-22A | (380 ... 415 V) 16 A(690 V) 16 A |
| Rated operational current AC-23A | (380 ... 415 V) 16 A(500 V) 16 A(690 V) 10 A |
| Rated operational power AC-23A | (380 ... 415 V) 7.5 kW(500 V) 7.5 kW(690 V) 7.5 kW |
| Rated operational voltage | Main Circuit 750 V |
| Rated short-circuit making capacity | (690 V AC) 0.705 kA |
| Rated short-time withstand current low voltage | for 1 s 0.5 kA |
| Tightening torque | Main Circuit 0.8 N·m |