BV certificateBV_2634H07559D0CB certificateCB_FR_602227ACCC certificateCCC_2013010304615752 CCC_2004010309133982Climatic withstandacc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification IICoil operating limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at 55 C) CConnecting capacity auxiliary circuitFlexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mmConnecting capacity main circuitFlexible with Cable End 2.5 ... 10 mm Rigid Cable 2.5 ... 16 mmConnecting terminals (delivered in open position) main polesM 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connectorConventional free-air thermal current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 C 65 A acc. to IEC 60947-5-1, q = 40 C 16 ACountry of OriginFrance (FR)CSA certificateCSA_1033838_LR056745cUL certificateUL_071301E39231Data sheet, technical information1SBC100122C0202_Ch02Declaration of conformity - CE1SBD250801U1000Degree of protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20DNV certificateDNV-GL_TAE00000TXE-nummer3227784EAC certificateEAC_RU C-FR ME77 B01010ETIM 4EC000066 - Magnet contactor, AC-switchingETIM 5EC000066 - Magnet contactor, AC-switchingETIM 6EC000066 - Power contactor, AC switchingGL certificateDNV-GL_TAE00000TXGOST certificateGOST_POCCFRME77B07175Lead time14 day(s)LOVAG certificateLOVAG_FR97009LR certificateLRS_9830011E4Made to orderNoMax electrical switching frequencyAC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 1200 cycles per hourMax mechanical switching frequency3600 cycles per hourMax operating altitude permissible3000 mNumber of auxiliary contacts NC0Number of auxiliary contacts NO1Number of main contacts NC0Number of main contacts NO3Object classification codeQProduct sales statusInactiveQuote onlyNoRated breaking capacity AC-3 acc. to IEC 60947-4-18 x Ie AC-3Rated control circuit voltage (Uc)50 Hz 220 230 V 60 Hz 230 240 VRated frequencySupply Circuit 50 Hz Supply Circuit 60 HzRated impulse withstand voltage (U imp)8 kVRated
| BV certificate | BV_2634H07559D0 |
| CB certificate | CB_FR_602227A |
| CCC certificate | CCC_2013010304615752 CCC_2004010309133982 |
| Climatic withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Coil operating limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at 55 C) C |
| Connecting capacity auxiliary circuit | Flexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mm |
| Connecting capacity main circuit | Flexible with Cable End 2.5 ... 10 mm Rigid Cable 2.5 ... 16 mm |
| Connecting terminals (delivered in open position) main poles | M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector |
| Conventional free-air thermal current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 C 65 A acc. to IEC 60947-5-1, q = 40 C 16 A |
| Country of Origin | France (FR) |
| CSA certificate | CSA_1033838_LR056745 |
| cUL certificate | UL_071301E39231 |
| Data sheet, technical information | 1SBC100122C0202_Ch02 |
| Declaration of conformity - CE | 1SBD250801U1000 |
| Degree of protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| DNV certificate | DNV-GL_TAE00000TX |
| E-nummer | 3227784 |
| EAC certificate | EAC_RU C-FR ME77 B01010 |
| ETIM 4 | EC000066 - Magnet contactor, AC-switching |
| ETIM 5 | EC000066 - Magnet contactor, AC-switching |
| ETIM 6 | EC000066 - Power contactor, AC switching |
| GL certificate | DNV-GL_TAE00000TX |
| GOST certificate | GOST_POCCFRME77B07175 |
| Lead time | 14 day(s) |
| LOVAG certificate | LOVAG_FR97009 |
| LR certificate | LRS_9830011E4 |
| Made to order | No |
| Max electrical switching frequency | AC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 1200 cycles per hour |
| Max mechanical switching frequency | 3600 cycles per hour |
| Max operating altitude permissible | 3000 m |
| Number of auxiliary contacts NC | 0 |
| Number of auxiliary contacts NO | 1 |
| Number of main contacts NC | 0 |
| Number of main contacts NO | 3 |
| Object classification code | Q |
| Product sales status | Inactive |
| Quote only | No |
| Rated breaking capacity AC-3 acc. to IEC 60947-4-1 | 8 x Ie AC-3 |
| Rated control circuit voltage (Uc) | 50 Hz 220 230 V 60 Hz 230 240 V |
| Rated frequency | Supply Circuit 50 Hz Supply Circuit 60 Hz |
| Rated impulse withstand voltage (U imp) | 8 kV |
| Rated insulation voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V |
| Rated making capacity AC-3 acc. to IEC 60947-4-1 | 10 x Ie AC-3 |
| Rated operational current AC-1 (Ie) | (690 V) 40 C 60 A (690 V) 55 C 60 A (690 V) 70 C 42 A |
| Rated operational current AC-15 (Ie) | (220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A |
| Rated operational current DC-13 (Ie) | (125 V) 1.1 / 138 A (24 V) 6 / 144 A (250 V) 0.55 / 138 A (48 V) 2.8 / 134 A (72 V) 2 / 144 A |
| Rated operational voltage | Main Circuit 690 V |
| RINA certificate | RINA_ELE128713XG001 |
| RMRS certificate | RMRS_0507015250 |
| RoHS information | 1SBD350054R1000 |
| RoHS status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| Short-circuit protective devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 63 A |
| Terminal type | Screw terminals |
| UL certificate | UL_071301E39231 |