Ambient air temperatureOperation -40 +70 C Storage -40 ... +85 CCCC certificateCCC_2009010907324502Conducted disturbances immunity acc. to IEC 61000-4-6Level 3 10 VConnecting capacity input circuitFlexible with Ferrule 0.2 ... 4 mm Rigid 0.2 ... 6 mmConnecting capacity input circuit UL/CSARigid 24-10 AWGConnecting capacity output circuitFlexible with Ferrule 0.2 ... 4 mm Rigid 0.2 ... 6 mmConnecting capacity output circuit UL/CSARigid 24-10 AWGcUL certificatecUL508_E174460cUR certificatecUR60950_E196145 cUR_ANSI_E317914Data sheet, technical information2CDC114062D0201Declaration of conformity - CE1SVD982008-0000Degree of protectionHousing IP20 Terminals IP20E-nummer5248136EAC certificateEAC_RU_C-DE.ME77.B.01651eClass7.0 27049002Electrical fast transient (burst immunity) acc. to IEC 61000-4-4Level 4 Power Supply Port Signal 4 kVElectromagnetic compatibility (EMC)Immunity - Class B Emission - Class BElectrostatic discharge (ESD immunity) acc. to IEC 61000-4-2Level 4 Air Discharge 15 kV Level 4 Contact Discharge 8 kVETIM 4EC002540 - DC-power supplyETIM 5EC002540 - DC-power supplyETIM 6EC002540 - DC-power supplyFunctionSwitch mode power supplyGOST certificateGOST_POCC_CN.AB76.B00924Input voltage (Uin)90 ... 264 V AC 120 ... 375 V DCMounting positionPosition 1Number of phases1Object classification codeTOutput current20 AOutput power480 WOutput voltage (U out )24 V DCPollution degree2Radiated electromagnetic field immunity acc. to IEC 61000-4-3Level 3 10 V/mRated frequency limits47 ... 63 HzRated input voltage (U IN )115 / 230 V ACRated insulation voltage (Ui)Input Circuit / Output Circuit 3 V Input Circuit / PE 2 VRated output current20 ARated output power480 WRated output voltage24 V DCRoHS information1SAA981023-4402RoHS statusFollowing EU Directive 2002/95/EC August 18, 2005 and amendmentSurge immunity acc. to IEC 61000-4-5Level 3 Line-to-Line 2 kV Level 4 Line-to-Ground 4 kVTightening torqueInput Circuit 1 Nm Output Circuit 0.62 NmTightening torque UL/CSAInput Circuit
| Ambient air temperature | Operation -40 +70 C Storage -40 ... +85 C |
| CCC certificate | CCC_2009010907324502 |
| Conducted disturbances immunity acc. to IEC 61000-4-6 | Level 3 10 V |
| Connecting capacity input circuit | Flexible with Ferrule 0.2 ... 4 mm Rigid 0.2 ... 6 mm |
| Connecting capacity input circuit UL/CSA | Rigid 24-10 AWG |
| Connecting capacity output circuit | Flexible with Ferrule 0.2 ... 4 mm Rigid 0.2 ... 6 mm |
| Connecting capacity output circuit UL/CSA | Rigid 24-10 AWG |
| cUL certificate | cUL508_E174460 |
| cUR certificate | cUR60950_E196145 cUR_ANSI_E317914 |
| Data sheet, technical information | 2CDC114062D0201 |
| Declaration of conformity - CE | 1SVD982008-0000 |
| Degree of protection | Housing IP20 Terminals IP20 |
| E-nummer | 5248136 |
| EAC certificate | EAC_RU_C-DE.ME77.B.01651 |
| eClass | 7.0 27049002 |
| Electrical fast transient (burst immunity) acc. to IEC 61000-4-4 | Level 4 Power Supply Port Signal 4 kV |
| Electromagnetic compatibility (EMC) | Immunity - Class B Emission - Class B |
| Electrostatic discharge (ESD immunity) acc. to IEC 61000-4-2 | Level 4 Air Discharge 15 kV Level 4 Contact Discharge 8 kV |
| ETIM 4 | EC002540 - DC-power supply |
| ETIM 5 | EC002540 - DC-power supply |
| ETIM 6 | EC002540 - DC-power supply |
| Function | Switch mode power supply |
| GOST certificate | GOST_POCC_CN.AB76.B00924 |
| Input voltage (Uin) | 90 ... 264 V AC 120 ... 375 V DC |
| Mounting position | Position 1 |
| Number of phases | 1 |
| Object classification code | T |
| Output current | 20 A |
| Output power | 480 W |
| Output voltage (U out ) | 24 V DC |
| Pollution degree | 2 |
| Radiated electromagnetic field immunity acc. to IEC 61000-4-3 | Level 3 10 V/m |
| Rated frequency limits | 47 ... 63 Hz |
| Rated input voltage (U IN ) | 115 / 230 V AC |
| Rated insulation voltage (Ui) | Input Circuit / Output Circuit 3 V Input Circuit / PE 2 V |
| Rated output current | 20 A |
| Rated output power | 480 W |
| Rated output voltage | 24 V DC |
| RoHS information | 1SAA981023-4402 |
| RoHS status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| Surge immunity acc. to IEC 61000-4-5 | Level 3 Line-to-Line 2 kV Level 4 Line-to-Ground 4 kV |
| Tightening torque | Input Circuit 1 Nm Output Circuit 0.62 Nm |
| Tightening torque UL/CSA | Input Circuit 9 inlb Output Circuit 5.5 inlb |
| UL certificate | UL508_E174460 |
| UR certificate | UR60950_E196145 UR_ANSI_E317914 |
| Wire stripping length | Input Circuit 8 mm Output Circuit 8 mm |