Accessory Size2Aux Condenser Strip Length1/2 IN OR 13 MMAux Contact Max Voltage Rating600VACAux Pilot Contact Current Rating1.2AAux Term Tightening Torque15 IN-LBS / 1.7 N-MAux Term TypeSCREWAux Term Wire Cap Max14 AWGBranch Switch RatingBRANCH CIRCUIT DISCONNECT SWITCHCSA List File155873CSA List Std 1C22.2 No. 182.1-13CSA ListingcCSAusCurrent Interrupting RatingSWITCH RATEDFrequency60 HzHP5Impact RatingIK09Keying Position7Load Break Abnormal Overload30 ALoad Break Normal Operation20 AMaterialPOLYMaximum Operating Temperature-C60CMaximum Operating Temperature-F140FMinimum Operating Temperature-C-40CMinimum Operating Temperature-F-40FMotor Switch RatingMOTOR CIRCUIT DISCONNECT SWITCHNEMA Watertightness3RNumber Of Auxiliary Contacts+2 AUXNumber of Notch Pos24Phase Condenser Strip Length7/16 IN OR 11 MMPhase Term Tightening Torque15 IN-LBS / 1.7 N-MPhase Term TypeSCREW TERMINALPhase Term Wire Cap Max THHN8 AWGPhase Term Wire Cap Max Type W8 AWGPhase Term Wire Cap Min THHN14 AWGPhase Term Wire Cap Min Type W14 AWGPrimary IP Rating55Prod Wire Temperature Rating60CProduct ColorBLUERated Current20 ARated Voltage250 VACShort Circuit Rating100 kA - CLOSE & WITHSTANDShort Circuit Rating Fusing100 kA 80 A (400%) RK1 NTDUl List FileE79796 VOLUME 8 SECTION 1Ul List Std 1UL 2682Ul List Std 2UL 1682Ul ListingULUl508 Pilot Rating2 @ code A600Voltage Color CodeORANGE
| Accessory Size | 2 |
| Aux Condenser Strip Length | 1/2 IN OR 13 MM |
| Aux Contact Max Voltage Rating | 600VAC |
| Aux Pilot Contact Current Rating | 1.2A |
| Aux Term Tightening Torque | 15 IN-LBS / 1.7 N-M |
| Aux Term Type | SCREW |
| Aux Term Wire Cap Max | 14 AWG |
| Branch Switch Rating | BRANCH CIRCUIT DISCONNECT SWITCH |
| CSA List File | 155873 |
| CSA List Std 1 | C22.2 No. 182.1-13 |
| CSA Listing | cCSAus |
| Current Interrupting Rating | SWITCH RATED |
| Frequency | 60 Hz |
| HP | 5 |
| Impact Rating | IK09 |
| Keying Position | 7 |
| Load Break Abnormal Overload | 30 A |
| Load Break Normal Operation | 20 A |
| Material | POLY |
| Maximum Operating Temperature-C | 60C |
| Maximum Operating Temperature-F | 140F |
| Minimum Operating Temperature-C | -40C |
| Minimum Operating Temperature-F | -40F |
| Motor Switch Rating | MOTOR CIRCUIT DISCONNECT SWITCH |
| NEMA Watertightness | 3R |
| Number Of Auxiliary Contacts | +2 AUX |
| Number of Notch Pos | 24 |
| Phase Condenser Strip Length | 7/16 IN OR 11 MM |
| Phase Term Tightening Torque | 15 IN-LBS / 1.7 N-M |
| Phase Term Type | SCREW TERMINAL |
| Phase Term Wire Cap Max THHN | 8 AWG |
| Phase Term Wire Cap Max Type W | 8 AWG |
| Phase Term Wire Cap Min THHN | 14 AWG |
| Phase Term Wire Cap Min Type W | 14 AWG |
| Primary IP Rating | 55 |
| Prod Wire Temperature Rating | 60C |
| Product Color | BLUE |
| Rated Current | 20 A |
| Rated Voltage | 250 VAC |
| Short Circuit Rating | 100 kA - CLOSE & WITHSTAND |
| Short Circuit Rating Fusing | 100 kA 80 A (400%) RK1 NTD |
| Ul List File | E79796 VOLUME 8 SECTION 1 |
| Ul List Std 1 | UL 2682 |
| Ul List Std 2 | UL 1682 |
| Ul Listing | UL |
| Ul508 Pilot Rating | 2 @ code A600 |
| Voltage Color Code | ORANGE |