ApprovalCSA, ULDrive isolation transformer3ph 7.5kVA 480V-240Y/139V 60Hz ALDutyGeneral dutyEfficiency regulationNot specified (USA)Enclosure dimensions21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)Enclosure finishANSI 61 grey, UL50Enclosure IR windowNoEnclosure PN (NPL)NH5-N3REnclosure typeType 3R / IP24Frequency60HzImpedance (std)3% - 6%Insulation class220°CMaterialAluminumMotor HPNot SelectedNameplateHPS standardNet weight (NPL)150 lb / 69 kgNumber of secondaries1 (6-pulse)PhaseThree phasePrimary connectionDeltaPrimary FCAN (NPL)1x5%Primary FCBN (NPL)1x5%Primary termination (NPL)Terminal blockPrimary voltage480DRating7.5 kVASecondary connectionWye-NSecondary termination (NPL)Mechanical lugsSecondary voltage240Y/139Seismic complianceIBC 2018 (Sds=2.0, z/h=0, lp=1.5)Sound level40 dBA (NEMA ST-20)Standard kVA7.5Temperature rise150°CThermal protective deviceNormally closed (all coils) thermostats with 200°C setpoint, typically built to orderVector configurationDyn1 (-30°)

Specifications

ApprovalCSA, UL
Drive isolation transformer3ph 7.5kVA 480V-240Y/139V 60Hz AL
DutyGeneral duty
Efficiency regulationNot specified (USA)
Enclosure dimensions21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)
Enclosure finishANSI 61 grey, UL50
Enclosure IR windowNo
Enclosure PN (NPL)NH5-N3R
Enclosure typeType 3R / IP24
Frequency60Hz
Impedance (std)3% - 6%
Insulation class220°C
MaterialAluminum
Motor HPNot Selected
NameplateHPS standard
Net weight (NPL)150 lb / 69 kg
Number of secondaries1 (6-pulse)
PhaseThree phase
Primary connectionDelta
Primary FCAN (NPL)1x5%
Primary FCBN (NPL)1x5%
Primary termination (NPL)Terminal block
Primary voltage480D
Rating7.5 kVA
Secondary connectionWye-N
Secondary termination (NPL)Mechanical lugs
Secondary voltage240Y/139
Seismic complianceIBC 2018 (Sds=2.0, z/h=0, lp=1.5)
Sound level40 dBA (NEMA ST-20)
Standard kVA7.5
Temperature rise150°C
Thermal protective deviceNormally closed (all coils) thermostats with 200°C setpoint, typically built to order
Vector configurationDyn1 (-30°)

DM007KD