BV certificateBV_2634H09651C0CB certificateCB_FR_602227BCCC certificateCCC_2003010304088236Climatic withstandacc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification IICoil operating limits(acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at 55 C) CConnecting capacity auxiliary circuitFlexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mmConventional free-air thermal current (Ith)acc. to IEC 60947-5-1, q = 40 C 16 ACSA certificateCSA_1041746cUL certificateUL_110105E48139AData sheet, technical information1SBC100122C0202_Ch03Declaration of conformity - CE1SBD250808U1000Degree of protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20DNV certificateDNV-GL_TAE00000TYETIM 4EC000196 - Contactor relayETIM 5EC000196 - Contactor relayETIM 6EC000196 - Contactor relayGL certificateDNV-GL_TAE00000TYGOST certificateGOST_POCCFRME01B03022LR certificateLRS_9830010E2Max mechanical switching frequency6000 cycles per hourMax operating altitude permissible3000 mMechanical durability> 20 millionNumber of auxiliary contacts NC2Number of auxiliary contacts NO4Object classification codeKRated control circuit voltage (Uc)50 Hz 110 V 60 Hz 110 120 VRated frequencySupply Circuit 50 Hz Supply Circuit 60 HzRated impulse withstand voltage (U imp)8 kVRated insulation voltage (Ui)acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 VRated operational current AC-15 (Ie)(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 ARated operational current DC-13 (Ie)(125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 ARated operational voltageMain Circuit 690 VRated short-time withstand current (Icw)for 0.1 s 140 A for 1 s 100 ARINA certificateRINA_ELE128713XG002RMRS certificateRMRS_0507015250RoHS information1SBD350056R1000RoHS statusFollowing EU Directive 2002/95/EC August 18, 2005 and amendmentShort-circuit protective devicesgG Type Fuses 10 ATerminal typeScrew terminalsUL certificateUL_110105E48139A
| BV certificate | BV_2634H09651C0 |
| CB certificate | CB_FR_602227B |
| CCC certificate | CCC_2003010304088236 |
| Climatic withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Coil operating limits | (acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at 55 C) C |
| Connecting capacity auxiliary circuit | Flexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mm |
| Conventional free-air thermal current (Ith) | acc. to IEC 60947-5-1, q = 40 C 16 A |
| CSA certificate | CSA_1041746 |
| cUL certificate | UL_110105E48139A |
| Data sheet, technical information | 1SBC100122C0202_Ch03 |
| Declaration of conformity - CE | 1SBD250808U1000 |
| Degree of protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| DNV certificate | DNV-GL_TAE00000TY |
| ETIM 4 | EC000196 - Contactor relay |
| ETIM 5 | EC000196 - Contactor relay |
| ETIM 6 | EC000196 - Contactor relay |
| GL certificate | DNV-GL_TAE00000TY |
| GOST certificate | GOST_POCCFRME01B03022 |
| LR certificate | LRS_9830010E2 |
| Max mechanical switching frequency | 6000 cycles per hour |
| Max operating altitude permissible | 3000 m |
| Mechanical durability | > 20 million |
| Number of auxiliary contacts NC | 2 |
| Number of auxiliary contacts NO | 4 |
| Object classification code | K |
| Rated control circuit voltage (Uc) | 50 Hz 110 V 60 Hz 110 120 V |
| Rated frequency | Supply Circuit 50 Hz Supply Circuit 60 Hz |
| Rated impulse withstand voltage (U imp) | 8 kV |
| Rated insulation voltage (Ui) | acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V |
| Rated operational current AC-15 (Ie) | (220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A |
| Rated operational current DC-13 (Ie) | (125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A |
| Rated operational voltage | Main Circuit 690 V |
| Rated short-time withstand current (Icw) | for 0.1 s 140 A for 1 s 100 A |
| RINA certificate | RINA_ELE128713XG002 |
| RMRS certificate | RMRS_0507015250 |
| RoHS information | 1SBD350056R1000 |
| RoHS status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| Short-circuit protective devices | gG Type Fuses 10 A |
| Terminal type | Screw terminals |
| UL certificate | UL_110105E48139A |