Ambient air temperatureOperation -25 . +50 C Storage -50 +80 CCCC certificate1SAA918001-3801Connecting capacity auxiliary circuit UL/CSAStranded 1/2x 14 ... 18 AWG Flexible 1/2x 14 ... 8 AWGContact rating UL/CSAB300 Q300Country of OriginSwitzerland (CH)cUL certificate1SAA918002-1701Data sheet, technical information1SBC100173C0201Declaration of conformity - CE1SAD938504-0021 1SAD938506-0037 1SAD938513-0003Degree of protectionIP20E-nummer3111370eClass7.0 27379201ETIM 4EC002498 - Accessories for low-voltage switch technologyETIM 5EC002498 - Accessories for low-voltage switch technologyETIM 6EC002498 - Accessories for low-voltage switch technologyGOST certificate1SAA918000-2703Lead time60 day(s)Made to orderNoNumber of auxiliary contacts NC1Number of auxiliary contacts NO1Object classification codeQProduct nameAuxiliary contactProduct sales statusActiveQuote onlyNoRated frequencyAuxiliary Circuit DC Auxiliary Circuit 50 Hz Auxiliary Circuit 60 HzRated impulse withstand voltage (U imp)Auxiliary Circuit 6 kVRated insulation voltage (Ui)690 VRated operational current AC-15 (Ie)(24 V) 3 A (120 V) 3 A (240 V) 2 A (380 / 400 V) 0.5 ARated operational current DC-13 (Ie)(24 V) 2.5 A (125 V) 0.55 A (250 V) 0,27 ARated operational voltage400 V AC 250 V DCRecommended screw driverPozidriv 2RoHS information1SAA918001-4402RoHS statusFollowing EU Directive 2002/95/EC August 18, 2005 and amendmentStandardsIEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1Suitable forMS325 MO325Suitable for product classManual Motor StarterTightening torqueAuxiliary Circuit 0.8 1.0 NmTightening torque UL/CSAAuxiliary Circuit 7 inlbUL certificate1SAA918002-1601Wire stripping lengthAuxiliary Circuit 8 mm
| Ambient air temperature | Operation -25 . +50 C Storage -50 +80 C |
| CCC certificate | 1SAA918001-3801 |
| Connecting capacity auxiliary circuit UL/CSA | Stranded 1/2x 14 ... 18 AWG Flexible 1/2x 14 ... 8 AWG |
| Contact rating UL/CSA | B300 Q300 |
| Country of Origin | Switzerland (CH) |
| cUL certificate | 1SAA918002-1701 |
| Data sheet, technical information | 1SBC100173C0201 |
| Declaration of conformity - CE | 1SAD938504-0021 1SAD938506-0037 1SAD938513-0003 |
| Degree of protection | IP20 |
| E-nummer | 3111370 |
| eClass | 7.0 27379201 |
| ETIM 4 | EC002498 - Accessories for low-voltage switch technology |
| ETIM 5 | EC002498 - Accessories for low-voltage switch technology |
| ETIM 6 | EC002498 - Accessories for low-voltage switch technology |
| GOST certificate | 1SAA918000-2703 |
| Lead time | 60 day(s) |
| Made to order | No |
| Number of auxiliary contacts NC | 1 |
| Number of auxiliary contacts NO | 1 |
| Object classification code | Q |
| Product name | Auxiliary contact |
| Product sales status | Active |
| Quote only | No |
| Rated frequency | Auxiliary Circuit DC Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz |
| Rated impulse withstand voltage (U imp) | Auxiliary Circuit 6 kV |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current AC-15 (Ie) | (24 V) 3 A (120 V) 3 A (240 V) 2 A (380 / 400 V) 0.5 A |
| Rated operational current DC-13 (Ie) | (24 V) 2.5 A (125 V) 0.55 A (250 V) 0,27 A |
| Rated operational voltage | 400 V AC 250 V DC |
| Recommended screw driver | Pozidriv 2 |
| RoHS information | 1SAA918001-4402 |
| RoHS status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| Standards | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 |
| Suitable for | MS325 MO325 |
| Suitable for product class | Manual Motor Starter |
| Tightening torque | Auxiliary Circuit 0.8 1.0 Nm |
| Tightening torque UL/CSA | Auxiliary Circuit 7 inlb |
| UL certificate | 1SAA918002-1601 |
| Wire stripping length | Auxiliary Circuit 8 mm |