Conventional free-air thermal currentq = 40 °C 200 AConventional thermal currentFully Enclosed 200 ADegree of protectionFront IP00Distance between phasesStandardHandle TypeHandle and shaft not includedLock typeNoMechanical durability20000Operating modeFront operatedPollution degree3Position of line terminalsTop In - Bottom OutBottom In - Top OutRated impulse withstand voltage12 kVRated insulation voltageacc. to IEC/EN 60664-1 1000 VRated operational current AC-21A(380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A(1000 V) 200 ARated operational current AC-22A(380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 ARated operational current AC-23A(380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 ARated operational power AC-23A(220 ... 240 V) 60 kW(400 ... 415 V) 110 kW(500 V) 132 kW(690 V) 200 kWRated operational voltageMain Circuit 1000 VRated short-circuit making capacity(690 V) 30 kARated short-time withstand current low voltagefor 1 s 8 kASpecial functionsNoSwitches operating mechanismMechanism at the End of the Switch03 (Left Side)Tightening torqueacc. IEC 60947-1 15 … 22 N·m
| Conventional free-air thermal current | q = 40 °C 200 A |
| Conventional thermal current | Fully Enclosed 200 A |
| Degree of protection | Front IP00 |
| Distance between phases | Standard |
| Handle Type | Handle and shaft not included |
| Lock type | No |
| Mechanical durability | 20000 |
| Operating mode | Front operated |
| Pollution degree | 3 |
| Position of line terminals | Top In - Bottom OutBottom In - Top Out |
| Rated impulse withstand voltage | 12 kV |
| Rated insulation voltage | acc. to IEC/EN 60664-1 1000 V |
| Rated operational current AC-21A | (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A(1000 V) 200 A |
| Rated operational current AC-22A | (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A |
| Rated operational current AC-23A | (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A |
| Rated operational power AC-23A | (220 ... 240 V) 60 kW(400 ... 415 V) 110 kW(500 V) 132 kW(690 V) 200 kW |
| Rated operational voltage | Main Circuit 1000 V |
| Rated short-circuit making capacity | (690 V) 30 kA |
| Rated short-time withstand current low voltage | for 1 s 8 kA |
| Special functions | No |
| Switches operating mechanism | Mechanism at the End of the Switch03 (Left Side) |
| Tightening torque | acc. IEC 60947-1 15 … 22 N·m |